TS500 Electronic Digital Display Temperature Sensor (Switch)
Data Download
Product Applications
1.HVAC and Building Automation
Application scenarios
Indoor environmental temperature monitoring: Measure the temperature of rooms in offices, shopping malls and hotels, and use it as an input signal for the building automation system to automatically adjust the cold and hot water valves or air valves at the air conditioning terminals.
Air duct/water pipe temperature measurement: Detect the air temperature of supply air and return air, as well as the supply and return water temperatures of chilled water and cooling water, for system energy-saving control and equipment protection.
Chiller/heat pump control: Monitor the temperature of the evaporator and condenser to ensure the efficient and safe operation of the unit.
2. General industrial equipment is matched with OEM
Application scenarios
Plastic machinery: Precise control of the barrel temperature of injection molding machines and extruders is the key to ensuring product quality.
Packaging machinery: Temperature control of the heat sealing knife to ensure the packaging is well sealed.
Food and beverage equipment: Temperature monitoring for baking equipment, filling lines, and pasteurization machines. It is usually required that the sensor material be food-grade stainless steel (such as SS316L).
Woodworking machinery: Temperature control of wood drying kilns and hot presses.
Experimental and testing equipment: constant temperature and humidity chambers, high and low temperature test chambers, ovens, muffle furnaces, etc., which have extremely high requirements for temperature accuracy and stability.
3. New energy and energy conservation field
Application scenarios
Heat pump system: Precise measurement of the temperatures on the water source side, ground source side and heating side is the core of the optimized control of the heat pump energy efficiency ratio (COP).
Solar thermal system: Monitor the temperature of the collector and the water storage tank, and intelligently control the start and stop of the circulating pump.
Thermal management of battery energy storage systems (BESS) : Monitor the ambient temperature of key points such as battery packs and PCS cabinets to start cooling fans or heaters. Note: Inside the battery compartment, due to the potential risk of hydrogen gas release from the battery, an explosion-proof type may be required. However, in external electrical cabinets or environmental monitoring, non-explosion-proof types can be applied.
Central air conditioning cooling tower control: Automatically start and stop the fan based on water temperature to achieve energy conservation.
4. Water Treatment and environmental Protection Engineering
Application scenarios
Wastewater treatment: Monitor the water temperature in the biochemical tank, as microbial activity is sensitive to temperature.
Constant temperature control of process water: In some production processes that require a constant temperature.
technical parameters
|
Parameter
|
Specification
|
|
Measuring range
|
-200... 400°C
|
|
Supply voltage
|
12... 30VDC
|
|
No-load current consumption
|
≤30mA, 24VDC
|
|
Switch output - Output type
|
PNP/NPN switchable, normally open/normally closed adjustable
|
|
Switch output - Switching load
|
<200mA/24VDC
|
|
Switch output - Response time
|
0.01 to 2 seconds (factory default)
|
|
Measurement accuracy
|
±1.0°C
|
|
Switch output - Current-type analog output
|
≤±0.5% range
|
|
Current-type analog output - Output type
|
4... 20mA can be set
|
|
Current-type analog output - Load RA
|
≤500Ω
|
|
Current-type analog output - Linearity
|
≤0.5% range
|
|
Communication output
|
IO-Link/RS485
|
|
Wiring protection
|
Reverse phase, overload, short circuit protection
|
|
Display - Design
|
Red 4-digit 12mm high-brightness LED
|
|
Display - Display range
|
-1999... 9999
|
|
Stability (annual drift)
|
≤±0.5°C
|
|
Temperature - Medium temperature
|
-20... 100°C (conventional type); - 200... 400°C (high and low temperature type)
|
|
Temperature - Ambient temperature
|
-20... 80°C
|
|
Temperature - Storage temperature
|
-30... 80°C
|
|
Materials - Meter head housing
|
Engineering plastic
|
|
Materials - Flame retardant grade
|
UL-94 V-0
|
|
Materials - Shell
|
Stainless steel 304
|
|
Materials - Medium contact part
|
Stainless steel 304
|
|
Protection grade
|
IP67
|
|
Cable exit method
|
M12x1 connector
|